低压电器的最小爬电距离
在微观环境中不同污染等级、不同工作电压、不同绝缘材料组别情况下最小爬电距离 (mm) | ||||||||||||||
电器的额定绝缘电压或工作电压V交流有效值或直流值④ | 印刷线路材料爬电距离,mm | 电器长期承受电压的爬电距离,mm | ||||||||||||
污染等级 | 污染等级 2 | 污染等级 3 | 污染等级 4 | |||||||||||
1 | 2 | 1 | ||||||||||||
① | ② | ① | 材料组别 | 材料组别 | 材料组别 | |||||||||
Ⅰ | Ⅱ | ⅢaⅢb | Ⅰ | Ⅱ | Ⅲa | Ⅲb | Ⅰ | Ⅱ | Ⅲa | Ⅲb | ||||
10 | 0.025 | 0.04 | 0.08 | 0.4 | 0.4 | 0.4 | 1 | 1 | 1 |
| 1.6 | 1.6 | 1.6 |
|
12.5 | 0.025 | 0.04 | 0.09 | 0.42 | 0.42 | 0.42 | 1.05 | 1.05 | 1.05 |
| 1.6 | 1.6 | 1.6 |
|
16 | 0.025 | 0.04 | 0.1 | 0.45 | 0.45 | 0.45 | 1.1 | 1.1 | 1.1 |
| 1.6 | 1.6 | 1.6 |
|
20 | 0.025 | 0.04 | 0.11 | 0.48 | 0.48 | 0.48 | 1.2 | 1.2 | 1.2 |
| 1.6 | 1.6 | 1.6 |
|
25 | 0.025 | 0.04 | 0.125 | 0.5 | 0.5 | 0.5 | 1.25 | 1.25 | 1.25 |
| 1.7 | 1.7 | 1.7 |
|
32 | 0.025 | 0.04 | 0.14 | 0.53 | 0.53 | 0.53 | 1.3 | 1.3 | 1.3 |
| 1.8 | 1.8 | 1.8 |
|
40 | 0.025 | 0.04 | 0.16 | 0.56 | 0.8 | 1.1 | 1.4 | 1.6 | 1.8 |
| 1.9 | 2.4 | 3 |
|
50 | 0.025 | 0.04 | 0.18 | 0.6 | 0.85 | 1.2 | 1.5 | 1.7 | 1.9 |
| 2 | 2.5 | 3.2 |
|
63 | 0.04 | 0.063 | 0.2 | 0.63 | 0.9 | 1.25 | 1.6 | 1.8 | 2 |
| 2.1 | 2.6 | 3.4 |
|
80 | 0.063 | 0.1 | 0.22 | 0.67 | 0.95 | 1.3 | 1.7 | 1.9 | 2.1 |
| 2.2 | 2.8 | 3.6 |
|
100 | 0.1 | 0.16 | 0.25 | 0.71 | 1 | 1.4 | 1.8 | 2 | 2.2 |
| 2.4 | 3.0 | 3.8 |
|
125,(127) | 0.16 | 0.25 | 0.28 | 0.75 | 1.05 | 1.5 | 1.9 | 2.1 | 2.4 |
| 2.5 | 3.2 | 4 |
|
160 | 0.25 | 0.4 | 0.32 | 0.8 | 1.1 | 1.6 | 2 | 2.2 | 2.5 |
| 3.2 | 4 | 5 |
|
200,(208) | 0.4 | 0.63 | 0.42 | 1 | 1.4 | 2 | 2.5 | 2.8 | 3.2 |
| 4 | 5 | 6.3 |
|
250 | 0.56 | 1 | 0.56 | 1.25 | 1.8 | 2.5 | 3.2 | 3.6 | 4 |
| 5 | 6.3 | 8 |
|
320 | 0.75 | 1.6 | 0.75 | 1.6 | 2.2 | 3.2 | 4 | 4.5 | 5 |
| 6.3 | 8 | 10 |
|
400,(415) | 1 | 2 | 1 | 2 | 2.8 | 4 | 5 | 5.6 | 6.3 |
| 8 | 10 | 12.5 |
|
500 | 1.3 | 2.5 | 1.3 | 2.5 | 3.6 | 5 | 6.3 | 7.1 | 8.0 |
| 10 | 12.5 | 16 |
|
630,(690) | 1.8 | 3.2 | 1.8 | 3.2 | 4.5 | 6.3 | 8 | 9 | 10 |
| 12.5 | 16 | 20 |
|
800,(830) | 2.4 | 4 | 2.4 | 4 | 5.6 | 8 | 10 | 11 | 12.5 |
| 16 | 20 | 25 |
|
1000 | 3.2 | 5 | 3.2 | 5 | 7.1 | 10 | 12.5 | 14 | 16 |
| 20 | 25 | 32 |
|
1250 |
|
| 4.2 | 6.3 | 9 | 12.5 | 16 | 18 | 20 |
| 25 | 32 | 40 | ③ |
1600 |
|
| 5.6 | 8 | 11 | 16 | 20 | 22 | 25 | ③ | 32 | 40 | 50 |
|
2000 |
|
| 7.5 | 10 | 14 | 20 | 25 | 28 | 32 |
| 40 | 50 | 63 |
|
2500 |
|
| 10 | 12.5 | 18 | 25 | 32 | 36 | 40 |
| 50 | 63 | 80 |
|
3200 |
|
| 12.5 | 16 | 22 | 32 | 40 | 45 | 50 |
| 63 | 80 | 100 |
|
注:①材料组别Ⅰ、Ⅱ、Ⅲa、Ⅲb。 ②材料级别Ⅰ、Ⅱ、Ⅲa。 ③此区域内爬电距离尚未规定,材料级别Ⅲb一般不推荐用于630V以上污染等级3,也不推荐用于污染等级4。 ④在工作电压为32V及以下的绝缘上不会产生漏电起痕现象,但是必须考虑电解腐蚀的可能性,为此也规定了最小爬电距离。 电器的额定绝缘电压或工作电压按R10数系选择。 | ||||||||||||||