注入公共连接点的谐波电流允许值
注入公共连接点的谐波电流允许值 | |||||||||||||||||||||||||
标准 电压 /kV | 基准短 路容量 /MVA | 谐波次数及谐波电流允许值/A | |||||||||||||||||||||||
2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | ||
0.38 | 10 | 78 | 62 | 39 | 62 | 26 | 44 | 19 | 21 | 16 | 28 | 13 | 24 | 11 | 12 | 9.7 | 18 | 8.6 | 16 | 7.8 | 8.9 | 7.1 | 14 | 6.5 | 12 |
6 | 100 | 43 | 34 | 21 | 34 | 14 | 24 | 11 | 11 | 8.5 | 16 | 7.1 | 13 | 6.1 | 6.8 | 5.3 | 10 | 4.7 | 9.0 | 4.3 | 4.9 | 3.9 | 7.4 | 3.6 | 6.8 |
10 | 100 | 26 | 20 | 16 | 20 | 8.5 | 15 | 6.4 | 6.8 | 5.1 | 9.3 | 4.3 | 7.9 | 3.7 | 4.1 | 3.2 | 6.0 | 2.8 | 5.4 | 2.6 | 2.9 | 2.3 | 4.5 | 2.1 | 4.1 |
35 | 250 | 15 | 12 | 7.7 | 12 | 5.1 | 8.8 | 3.8 | 4.1 | 3.1 | 5.6 | 2.6 | 4.7 | 2.2 | 2.5 | 1.9 | 3.6 | 1.7 | 3.2 | 1.5 | 1.8 | 1.4 | 2.7 | 1.3 | 2.5 |
66 | 500 | 16 | 13 | 8.1 | 13 | 5.4 | 9.3 | 4.1 | 4.3 | 3.5 | 5.9 | 2.7 | 5.0 | 2.3 | 2.6 | 2.0 | 3.8 | 1.8 | 3.4 | 1.6 | 1.9 | 1.5 | 2.8 | 1.4 | 2.6 |
110 | 750 | 12 | 9.6 | 6.0 | 9.6 | 4.0 | 6.8 | 3.0 | 3.0 | 2.4 | 4.3 | 2.0 | 3.7 | 1.7 | 1.9 | 1.5 | 2.8 | 1.3 | 2.5 | 1.2 | 1.4 | 1.1 | 2.1 | 1.0 | 1.9 |