注入公共连接点的谐波电流允许值
注入公共连接点的谐波电流允许值 | ||||||||||||
标准电压 /kV | 基准短路容量 /MVA | 谐波次数及谐波电流允许值/A | ||||||||||
2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | ||
0.38 | 10 | 78 | 62 | 39 | 62 | 26 | 44 | 19 | 21 | 16 | 28 | 13 |
6 | 100 | 43 | 34 | 21 | 34 | 14 | 24 | 11 | 11 | 8.5 | 16 | 7.1 |
10 | 100 | 26 | 20 | 13 | 20 | 8.5 | 15 | 6.4 | 6.8 | 5.1 | 9.3 | 4.3 |
35 | 250 | 15 | 12 | 7.7 | 12 | 5.1 | 8.8 | 3.8 | 4.1 | 3.1 | 5.6 | 2.6 |
66 | 500 | 16 | 13 | 8.1 | 13 | 5.4 | 9.3 | 4.1 | 4.3 | 3.3 | 5.9 | 2.7 |
110 | 750 | 12 | 9.6 | 6.0 | 9.6 | 4.0 | 6.8 | 3.0 | 3.2 | 2.4 | 4.3 | 2.0 |