10kV聚乙烯绝缘电力电缆的供电距离
10kV聚乙烯绝缘电力电缆的供电距离 (km) | |||||||
截面(mm2) | 允许负荷 | 电压损失 (%/MW·km) cosφ=0.9 | 允许负荷下的供电距离(km) | ||||
S (MVA) | P (MW) | 允许电压损失(%) | |||||
3 | 5 | 7 | |||||
铝 | 35 | 2.165 | 1.949 | 1.074 | 1.433 | 2.389 | 3.344 |
50 | 2.511 | 2.260 | 0.756 | 1.735 | 2.892 | 4.049 | |
70 | 3.188 | 2.806 | 0.559 | 1.913 | 3.188 | 4.463 | |
95 | 3.724 | 3.352 | 0.423 | 2.116 | 3.526 | 4.937 | |
120 | 4.244 | 3.802 | 0.343 | 2.300 | 3.840 | 5.368 | |
150 | 4.763 | 4.287 | 0.283 | 2.473 | 4.121 | 5.770 | |
185 | 5.369 | 4.832 | 0.236 | 2.631 | 4.385 | 6.138 | |
240 | 6.235 | 5.612 | 0.190 | 2.814 | 4.689 | 6.565 | |
铜 | 35 | 2.771 | 2.494 | 0.667 | 1.777 | 2.961 | 4.146 |
50 | 3.291 | 2.962 | 0.487 | 2.080 | 3.466 | 4.853 | |
70 | 3.894 | 3.586 | 0.359 | 2.330 | 3.884 | 5.437 | |
95 | 4.763 | 4.287 | 0.276 | 2.535 | 4.226 | 5.916 | |
120 | 5.369 | 4.832 | 0.227 | 2.735 | 4.558 | 6.382 | |
150 | 6.602 | 5.456 | 0.190 | 2.984 | 4.823 | 6.753 | |
185 | 6.842 | 6.158 | 0.162 | 3.007 | 5.012 | 7.017 | |
240 | 7.881 | 7.093 | 0.133 | 3.810 | 5.300 | 7.420 | |
注:1.电缆线路为埋地敷设,T=25℃、线芯工作温度θ=90℃、土壤电阻率ρ=1.2℃·m/W。 2.10kV用户补偿后的功率因数为0.9。 3.允许负荷下的供电距离系按线路末端集中负荷计算,当实际工程为分布负荷时,供电距离降大于表中的数据。 | |||||||