潮湿场所电击危险程度分级
潮湿场所电击危险程度分级 | |||
分级 | 浴室 | 游泳池 | 桑拿浴 |
0区 | 浴盆或淋浴器下 | 水池内 | — |
1区 | 浴盆外边,或喷头0.6m,高2.25m范围 | 池外2m,高2.5m范围内 | 加热器边外0.5m,高距顶0.3m范围内 |
2区 | 1区外0.6m,高2.25m范围内 | 1区外1.5m,高2.5m范围内 | 1区以外,高0.5m范围内 |
3区 | 2区外2.4m,高2.25m范围内 | — | 1区高度以上至顶0.3m处范围内 |
4区 | — | — | 至顶板0.3m范围内 |
潮湿场所电击危险程度分级 | |||
分级 | 浴室 | 游泳池 | 桑拿浴 |
0区 | 浴盆或淋浴器下 | 水池内 | — |
1区 | 浴盆外边,或喷头0.6m,高2.25m范围 | 池外2m,高2.5m范围内 | 加热器边外0.5m,高距顶0.3m范围内 |
2区 | 1区外0.6m,高2.25m范围内 | 1区外1.5m,高2.5m范围内 | 1区以外,高0.5m范围内 |
3区 | 2区外2.4m,高2.25m范围内 | — | 1区高度以上至顶0.3m处范围内 |
4区 | — | — | 至顶板0.3m范围内 |