控制信号、弱电线路在线槽内允许容纳根数
控制信号、弱电线路在线槽内允许容纳根数 | |||||||||||||
型号 | 标称截面 (mm2) | 金属线槽容纳导线根数 | 塑料线槽容纳导线根数 | ||||||||||
墙上或支架安装 | 地面内安装 | 墙上或支架安装 | |||||||||||
45×30 | 55×40 | 45×45 | 120×65 | 50×25 | 70×36 | 20×12.5 | 40×30 | 60×30 | 80×50 | 100×50 | 120×50 | ||
BV | 0.75 | 133 | 223 | 205 | 826 | 122 | 257 | 21 | 118 | 180 | 416 | 522 | 629 |
1.0 | 120 | 201 | 184 | 743 | 110 | 231 | 17 | 106 | 162 | 375 | 470 | 261 | |
1.5 | 67 | 112 | 102 | 413 | 61 | 128 | 10 | 59 | 90 | 208 | 261 | 314 | |
2.5 | 54 | 91 | 84 | 338 | 50 | 105 | 8 | 48 | 74 | 170 | 213 | 257 | |
RVS | 2×0.2 | 46 | 77 | 71 | 286 | 42 | 89 | 7 | 41 | 62 | 144 | 181 | 218 |
2×0.5 | 33 | 56 | 51 | 206 | 30 | 64 | 5 | 29 | 45 | 104 | 130 | 157 | |
2×0.75 | 23 | 38 | 35 | 143 | 21 | 44 | 3 | 20 | 31 | 72 | 90 | 109 | |
2×1.0 | 20 | 33 | 30 | 124 | 18 | 38 | 3 | 17 | 27 | 62 | 78 | 94 | |
2×1.5 | 16 | 28 | 25 | 103 | 15 | 32 | 2 | 14 | 22 | 52 | 65 | 78 | |
2×2.5 | 9 | 15 | 14 | 58 | 8 | 18 | 1 | 8 | 13 | 29 | 36 | 44 | |
SDYC SYV SS | 75-5-5 75-5-4 75-5-4 | 6 | 9 | 9 | 34 | 6 | 13 | — | 5 | 7 | 16 | 20 | 25 |
75-7-5 75-7-4 75-7-4 | 2 | 4 | 4 | 18 | 3 | 6 | — | 2 | 3 | 7 | 9 | 11 | |
75-9-5 75-9-4 75-9-4 | 2 | 3 | 2 | 10 | 2 | 4 | — | 2 | 2 | 6 | 7 | 8 | |