铁损干燥法所需励磁线圈及电流选择
铁损干燥法所需励磁线圈及电流选择 | |||||||||
变压器的容量 (kVA) | 外壳周长 (m) | 周围环境温度 (℃) | 励磁线圈的电压 (V) | ||||||
65 | 125 | 220 | |||||||
线匝数 | 电流(A) | 线匝数 | 电流(A) | 线匝数 | 电流(A) | ||||
外 壳 有 保 温 层 | 100 | 2.4 | 0 | 47 | 37 |
|
|
|
|
15 | 52 | 31 |
|
|
|
| |||
30 | 53 | 26 |
|
|
|
| |||
180 | 2.54 | 0 | 45 | 42 |
|
|
|
| |
15 | 49 | 35 |
|
|
|
| |||
30 | 50 | 29 |
|
|
|
| |||
320 | 2.75 | 0 | 42 | 60 |
|
|
|
| |
15 | 44 | 42 |
|
|
|
| |||
30 | 47 | 35 |
|
|
|
| |||
560 | 3.52 | 0 | 34 | 80 | 63 | 43 |
|
| |
15 | 35 | 68 | 67 | 37 |
|
| |||
30 | 38 | 56 | 71 | 30 |
|
| |||
750 | 3.94 | 0 | 29 | 105 | 54 | 57 | 100 | 32 | |
15 | 31 | 89 | 57 | 48 | 105 | 28 | |||
30 | 33 | 74 | 61 | 40 | 112 | 23 | |||
1000 | 4.04 | 0 | 29 | 124 | 53 | 67 | 98 | 37 | |
15 | 30 | 107 | 56 | 58 | 103 | 31 | |||
30 | 32 | 88 | 60 | 48 | 110 | 29 | |||
1800 |
| 0 |
|
| 44 | 152 |
|
| |
15 |
|
| 49 | 114 |
|
| |||
30 |
|
| 50 | 107 |
|
| |||
外 壳 无 保 温 层 | 100 | 2.4 | 0 | 30 | 91 |
|
|
|
|
15 | 36 | 77 |
|
|
|
| |||
30 | 39 | 64 |
|
|
|
| |||
180 | 2.54 | 0 | 33 | 103 |
|
|
|
| |
15 | 34 | 88 |
|
|
|
| |||
30 | 37 | 72 |
|
|
|
| |||
320 | 2.75 | 0 | 30 | 124 |
|
|
|
| |
15 | 32 | 106 |
|
|
|
| |||
30 | 34 | 87 |
|
|
|
| |||
560 | 3.52 | 0 | 24 | 198 | 45 | 107 |
|
| |
15 | 26 | 168 | 47 | 91 |
|
| |||
30 | 28 | 138 | 51 | 75 |
|
| |||
750 | 3.94 | 0 | 21 | 264 | 39 | 143 | 71 | 66 | |
15 | 22 | 224 | 42 | 121 | 76 | 56 | |||
30 | 24 | 184 | 45 | 100 | 82 | 46 | |||
1000 | 4.04 | 0 | 21 | 315 | 38 | 170 | 70 | 79 | |
15 | 22 | 265 | 41 | 144 | 75 | 66 | |||
30 | 24 | 219 | 44 | 119 | 81 | 55 | |||