油浸式变压器过载运行时允许过载率
油浸式变压器过载运行时允许过载率β2 | ||||||||||||||||||
(1)油浸自冷和风冷,热时间常数3h | ||||||||||||||||||
等效起始负载率β1 | 0.50 | 0.70 | 0.90 | 1.00 | ||||||||||||||
冷却介质温度(℃) | 0 | 10 | 20 | 30 | 40 | 0 | 10 | 20 | 30 | 40 | 0 | 10 | 20 | 30 | 40 | 0 | 20 | |
过载时间t2 (h) | 0.5 | + | + | + | 1.92 | 1.77 | + | + | 1.93 | 1.78 | 1.58 | + | 1.88 | 1.69 | 1.26 | — | 1.93 | — |
1 | + | 1.92 | 1.80 | 1.68 | 1.54 | 1.94 | 1.82 | 1.70 | 1.55 | 1.37 | 1.81 | 1.67 | 1.50 | 1.10 | — | — | — | |
2 | 1.73 | 1.63 | 1.53 | 1.42 | 1.30 | 1.67 | 1.57 | 1.46 | 1.34 | 1.18 | 1.58 | 1.47 | 1.32 | 0.99 | — | 1.52 | — | |
4 | 1.48 | 1.39 | 1.31 | 1.21 | 1.10 | 1.45 | 1.36 | 1.27 | 1.16 | 1.03 | 1.40 | 1.30 | 1.18 | 0.95 | — | — | — | |
8 | 1.31 | 1.23 | 1.15 | 1.06 | 0.96 | 1.30 | 1.22 | 1.13 | 1.04 | 0.92 | 1.28 | 1.19 | 1.09 | 0.93 | — | — | — | |
24 | 1.16 | 1.03 | 1.00 | 0.91 | 0.82 | 1.16 | 1.08 | 1.00 | 0.91 | 0.82 | 1.16 | 1.08 | 1.00 | 0.91 | — | 1.16 | — | |
(2)强油循环风冷和水冷,热时间常数1.5h~2h | ||||||||||||||||||
等效起始负载率β1 | 0.50 | 0.70 | 0.90 | 1.00 | ||||||||||||||
冷却介质温度(℃) | 0 | 10 | 20 | 30 | 40 | 0 | 10 | 20 | 30 | 40 | 0 | 10 | 20 | 30 | 40 | 0 | 20 | |
过载时间t2 (h) | 0.5 | 1.73 | 1.65 | 1.57 | 1.49 | 1.39 | 1.68 | 1.60 | 1.51 | 1.42 | 1.31 | 1.60 | 1.52 | 1.41 | 1.20 | — | 1.55 | — |
1 | 1.61 | 1.53 | 1.44 | 1.36 | 1.27 | 1.55 | 1.48 | 1.39 | 1.31 | 1.20 | 1.49 | 1.42 | 1.31 | 1.11 | — | — | — | |
2 | 1.45 | 1.38 | 1.30 | 1.23 | 1.14 | 1.42 | 1.36 | 1.27 | 1.19 | 1.10 | 1.38 | 1.31 | 1.21 | 1.04 | — | 1.36 | — | |
4 | 1.32 | 1.26 | 1.18 | 1.11 | 1.03 | 1.31 | 1.24 | 1.16 | 1.09 | 1.00 | 1.29 | 1.22 | 1.13 | 0.99 | — | 1.25 | — | |
8 | 1.23 | 1.17 | 1.09 | 1.02 | 0.94 | 1.22 | 1.16 | 1.08 | 1.01 | 0.93 | 1.22 | 1.15 | 1.06 | 0.95 | — | — | — | |
24 | 1.14 | 1.07 | 1.00 | 0.92 | 0.84 | 1.14 | 1.07 | 1.00 | 0.92 | 0.84 | 1.14 | 1.07 | 1.00 | 0.92 | — | 1.14 | — | |
注:“+”β2表示≥2.0。 | ||||||||||||||||||