ZW1系列智能型万能式断路器
脱扣器整定值 | ||||
负载监测 | 长延时保护 | 短延时保护 | 瞬时保护 | 接地保护 |
I c1 = In I c2 = In | I r1 = In t L = 480s | I r2 = 6In t s = 0 . 2s | I r3 = 15In ( ≥ 20kA ) | I r4 = 0 . 8In t G = 0 . 2s |
注 :接地保护,如用户无此项保护,一般不设定。 | ||||
脱扣器整定值 | ||||
负载监测 | 长延时保护 | 短延时保护 | 瞬时保护 | 接地保护 |
I c1 = In I c2 = In | I r1 = In t L = 480s | I r2 = 6In t s = 0 . 2s | I r3 = 15In ( ≥ 20kA ) | I r4 = 0 . 8In t G = 0 . 2s |
注 :接地保护,如用户无此项保护,一般不设定。 | ||||