三相380V架空裸铝线截面选择
三相380V架空裸铝线截面选择 | |||||||||||
送电距离(km) | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.5 | 2.0 | 2.5 | 3.0 | 4.0 | 5.0 |
输送容量(kW) | 裸铝线截面(mm2) | ||||||||||
2 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 25 | 35 |
3 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 25 | 25 | 35 | 50 |
4 | 16 | 16 | 16 | 16 | 16 | 16 | 25 | 35 | 35 | 50 | 70 |
5 | 16 | 16 | 16 | 16 | 16 | 25 | 25 | 35 | 50 | 70 |
|
6 | 16 | 16 | 16 | 16 | 16 | 25 | 35 | 50 | 70 |
|
|
8 | 16 | 16 | 16 | 16 | 25 | 35 | 50 | 70 |
|
|
|
10 | 16 | 16 | 16 | 25 | 35 | 50 | 70 |
|
|
|
|
15 | 16 | 16 | 25 | 35 | 50 | 70 |
|
|
|
|
|
20 | 16 | 25 | 35 | 50 | 70 |
|
|
|
|
|
|
25 | 16 | 25 | 50 | 70 |
|
|
|
|
|
|
|
30 | 16 | 35 | 70 | 95 |
|
|
|
|
|
|
|
40 | 25 | 50 | 95 |
|
|
|
|
|
|
|
|
45 | 25 | 70 |
|
|
|
|
|
|
|
|
|
50 | 35 | 70 |
|
|
|
|
|
|
|
|
|
60 | 50 | 95 |
|
|
|
|
|
|
|
|
|
70 | 50 |
|
|
|
|
|
|
|
|
|
|
80 | 70 |
|
|
|
|
|
|
|
|
|
|
90 | 70 |
|
|
|
|
|
|
|
|
|
|
100 | 70 |
|
|
|
|
|
|
|
|
|
|
注:线间距离为0.4m,cosφ为0.8,电压降不超过额定值的10%。 | |||||||||||