SDH-0.66系列电流互感器技术数据 | ||||||||
规格型式 | SDH-02 (BH-30Ⅰ) | SDH-01 (BH-40Ⅰ) | SDH-1 (BH-50Ⅱ) | SDH-2 (BH-60Ⅱ) | SDH-3 (BH-80Ⅱ) | SDH-4 (BH-100Ⅱ) | SDH-5 (BH-120×50Ⅱ) | SDH-6 (BH-180Ⅱ) |
母排规格/根数 | 30×10/1 | 40×10/1 | 50×10/1-2 | 60×10/1-2 | 80×10/1-2 | 100×10/1-2 | 120×10/1-3 | 180×10/1-2 |
准确级 | 0.5 1 | 0.5 1 | 0.2 0.5 | 0.2 0.5 | 0.2 0.5 | 0.2 0.5 | 0.2 0.5 | 0.2 0.5 |
额定电流比 | 额定负荷(VA) | |||||||
15/5 (5) | 2.5 | 2.5 |
|
|
|
|
|
|
20/5 (4) | 2.5 | 2.5 |
|
|
|
|
|
|
25/5~30/5 (3) | 2.5 | 2.5 |
|
|
|
|
|
|
40/5~60/5 (2) | 2.5 | 2.5 |
|
|
|
|
|
|
75/5 | 2.5 | 2.5 |
|
|
|
|
|
|
100/5 | 2.5 | 2.5 |
|
|
|
|
|
|
150/5 | 2.5 | 2.5 | 2.5 | 2.5 |
|
|
|
|
200/5~400/5 | 5 | 5 | 5 | 5 | 5 | 5 |
|
|
500/5~800/5 |
| 10 | 10 | 10 | 10 | 10 |
|
|
1000/5 |
|
| 15 | 15 | 15 | 15 | 15 |
|
1200/5~1500/5 |
|
| 20 | 20 | 20 | 20 | 20 | 20 |
2000/5 |
|
|
| 40 | 40 | 40 | 40 | 40 |
2500/5 |
|
|
|
| 40 | 40 | 40 | 40 |
3000/5 |
|
|
|
|
| 40 | 40 | 40 |
4000/5 |
|
|
|
|
| 40 | 40 | 40 |
5000/5 |
|
|
|
|
|
| 40 | 40 |
| 额定负荷(Ω) | |||||||
5/1 (3) | 0.1 |
|
|
|
|
|
|
|
10/1 (2) | 0.1 |
|
|
|
|
|
|
|
15/1~25/1 | 0.1 |
|
|
|
|
|
|
|
30/1~40/1 | 0.1 | 0.1 | 0.2 | 0.2 |
|
|
|
|
50/1~100/1 | 0.2 | 0.2 | 2.5 | 2.5 | 2.5 |
|
|
|
150/1 | 2.5 | 2.5 | 5 | 5 | 5 |
|
|
|
200/1~300/1 | 5 | 5 | 10 | 10 | 10 | 10 | 10 |
|
400/1~800/1 |
| 10 | 10 | 10 | 10 | 10 | 10 |
|
1000/1 |
|
|
| 20 | 20 | 20 | 20 | 20 |
1200/1 |
|
|
| 20 | 20 | 20 | 20 | 20 |
1500/1 |
|
|
|
| 20 | 20 | 20 | 20 |
2000/1 |
|
|
|
|
| 20 | 20 | 20 |
2500/1 |
|
|
|
|
| 20 | 20 | 20 |
3000/1 |
|
|
|
|
| 20 | 20 | 20 |
4000/1 |
|
|
|
|
|
| 20 | 20 |
注:额定电流比栏中括号内所标注为穿心匝数,未标注的全为1匝。 | ||||||||