控制箱(DCP)外部接线导线规格
控制箱(DCP)外部接线导线规格表 | |||
序号 | 监控功能 | 状态 | 导线规格 |
1 | 启停控制信号 | DO | 2×(0.75~1.5) |
2 | 工作状态信号 | DI | 2×(0.75~1.5) |
3 | 故障状态信号 | DI | 2×(0.75~1.5) |
4 | 手动/自动转换信号 | DI | 2×(0.75~1.5) |
5 | 远程/就地控制信号 | DI | 2×(0.75~1.5) |
6 | 故障报警信号 | DI | 2×(0.75~1.5) |
7 | 过滤网淤塞信号 | DI | 2×(0.75~1.5) |
8 | 风机压差监测信号 | DI | 2×(0.75~1.5) |
9 | 电动调节风门 | AO | 4×(0.75~1.5) |
10 | 电动调节蒸汽阀 | AO | 4×(0.75~1.5) |
11 | 电动调节阀 | AO | 4×(0.75~1.5) |
12 | 电动蝶阀 | DI、AO | 8×(0.75~1.5) |
13 | 防冻开关信号 | DI | 2×(0.75~1.5) |
14 | 水流量信号 | AI | 4×(0.75~1.5) |
15 | 水流开关信号 | DI | 2×(0.75~1.5) |
16 | 旁路电动调节阀 | AO | 4×(0.75~1.5) |
17 | 风管静压 | AI | 2×(0.75~1.5) |
18 | 新风、回风、送风温度 | AI | 2×(0.75~1.5) |
19 | 新风、回风、送风湿度 | AI | 4×(0.75~1.5) |
20 | 送(回)水温度 | AI | 2×(0.75~1.5) |
21 | 低压保护信号 | DI | 2×(0.75~1.5) |
22 | 变频器开关信号 | DO | 2×(0.75~1.5) |
23 | 变频器故障报警 | DI | 2×(0.75~1.5) |
24 | 变频器频率 | AI | 2×(0.75~1.5) |
25 | 变频器控制 | AO | 2×(0.75~1.5) |
26 | 照明控制 | DI、DO | 6×(0.75~1.5) |
27 | 巡更点 | DI | 2×(0.75~1.5) |
28 | 门禁开关 | DI | 2×(0.75~1.5) |
29 | 电梯状态 | DI | 2×(0.75~1.5) |
30 | CO2浓度 | AI | 4×(0.75~1.5) |
31 | 水位检测 | DI | 2×(0.75~1.5) |
32 | 电气参数检测 | AI | 2×(0.75~1.5) |
33 | 电量计量 | AI | 2×(0.75~1.5) |
34 | 水流信号 | AI | 4×(0.75~1.5) |
注:1.数字量(DI/DO)信号线采用BV、BVV、RV、RVV、KVV、BVR型导线; 2.模拟量(AI/AO)信号线采用RVVP屏蔽线。 | |||