人工接地装置工频接地电阻值
人工接地装置工频接地电阻值 | ||||||||
形式 | 简图 | 材料尺寸(mm)及用量(m) | 土壤电阻率(Ω·m) | |||||
圆钢 f20 | 钢管 f50 | 角钢 50×50×5 | 扁钢 40×4 | 100 | 250 | 500 | ||
工频接地电阻(Ω) | ||||||||
单根 |
| 2.5 | 2.5
|
2.5 |
| 30.2 37.2 32.4 | 75.4 92.9 81.1 | 151 186 162 |
2根 |
|
| 5.0
|
5.0 | 2.5 2.5 | 10.0 10.5 | 25.1 26.2 | 50.2 52.5 |
3根 |
|
| 7.5
|
7.5 | 5.0 5.0 | 6.65 6.92 | 16.6 17.3 | 33.2 34.6 |
4根 |
|
| 10.0
|
10.0 | 7.5 7.5 | 5.08 5.29 | 12.7 13.2 | 25.4 26.5 |
5根 |
|
| 12.5
|
12.5 | 20.0 20.0 | 4.18 4.35 | 10.5 10.9 | 20.9 21.8 |
6根 |
| 15.0
|
15.0 | 25.0 25.0 | 3.58 3.73 | 8.95 9.32 | 17.9 18.6 | |
8根 |
| 20.0
|
20.0 | 35.0 35.0 | 2.81 2.93 | 7.03 7.32 | 14.1 14.6 | |
10根 |
| 25.0
|
25.0 | 45.0 45.0 | 2.35 2.45 | 5.87 6.12 | 11.7 12.2 | |
15根 |
| 37.5
|
37.5 | 70.0 70.0 | 1.75 1.82 | 4.36 4.56 | 8.73 9.11 | |
20根 |
| 50.0
|
50.0 | 95.0 95.0 | 1.45 1.52 | 3.62 3.79 | 7.24 7.58 | |