COMO M系列负荷开关
COMO M 系列负荷开关电气和机械特性 | |||||||
约定发热电流 Ith ( 40 ℃, A ) | 20 | 25 | 32 | 40 | 63 | 80 | 100 |
外壳尺寸 | M1 | M1 | M1 | M1 | M2 | M2 | M2 |
额定绝缘电压 Ui ( V ) | 800 | 800 | 800 | 800 | 800 | 800 | 800 |
绝缘强度 50Hz 1min ( kV ) | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
额定冲击耐受电压 Uimp ( kV ) | 8 | 8 | 8 | 8 | 8 | 8 | 8 |
额定工作电流 In ① | |||||||
400V AC 21A — AC 22A ( A ) | 20 | 25 | 32 | 40 | 63 | 80 | 100 |
AC 23A ( A ) | 20 | 25 | 32 | 40 | 63 | 80 | 80 |
500V AC 21A — AC 22A ( A ) | 20 | 25 | 32 | 40 | 63 | 80 | 100 |
AC 23A ( A ) | 16 | 20 | 25 | 32 | 50 | 63 | 63 |
690V ③ AC 21A — AC 22A ( A ) | 20 | 25 | 32 | 40 | 63 | 80 | 100 |
AC 23A ( A ) | 16 | 20 | 20 | 20 | 50 | 50 | 50 |
电动机功率② | |||||||
400V AC ( kW ) | 5 . 5 | 7 . 5 | 9 | 15 | 18 . 5 | 22 | 30 |
500V AC ( kW ) | 7 . 5 | 9 | 11 | 15 | 18 . 5 | 18 . 5 | 22 |
690V AC ( kW ) | 9 | 11 | 11 | 11 | 18 . 5 | 18 . 5 | 22 |
400V AC — AC23A ( kW ) | 9 | 11 | 15 | 18 . 5 | 30 | 40 | 40 |
500V AC — AC23A ( kW ) | 9 | 11 | 15 | 18 . 5 | 33 | 40 | 40 |
690V AC — AC23A ( KW ) | 11 | 15 | 15 | 15 | 45 | 45 | 45 |
允许的短期电流 Icw1s ( A ) 短路接通容量 Icm ( A ,峰值) | 1260 1800 | 1260 1800 | 1260 1800 | 1260 1800 | 1500 2100 | 1500 2100 | 1500 2100 |
接通与断开特性 | |||||||
断开容量 400V AC 23A ( A ) 接通容量 400V AC 23A ( A ) | 160 200 | 200 250 | 256 320 | 320 400 | 504 630 | 640 800 | 640 800 |
寿命 | |||||||
机械 ( 操作循环次数,次) | 100000 | 100000 | 100000 | 100000 | 30000 | 30000 | 30000 |
电气 ( 操作循环次数,次) | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 |
连接 | |||||||
对于 Ith 的最小 / 最大铜缆截面积( mm2 ) | 2 . 5 / 16 | 2 . 5 / 16 | 4 / 16 | 6 / 16 | 10 / 50 | 16 / 50 | 25 / 50 |
质量 ( kg ) | |||||||
3 极 | 0 . 13 | 0 . 13 | 0 . 13 | 0 . 13 | 0 . 25 | 0 . 25 | 0 . 25 |
注 :① A 类型,频繁操作;②功率值仅作参考;③带隐藏端子。 | |||||||