SIRCOVER—VE系列转换开关
SIRCOVER — VE 系列负荷开关电气和机械特性 | |||||
约定发热电流 ( 40 ℃, A ) | 250 | 400 | 630 | 800 | |
额定绝缘电压 Ui ( V ) | 750 | 1000 | 1000 | 1000 | |
绝缘强度 50Hz1min ( V ) | 5000 | 8000 | 8000 | 8000 | |
额定冲击耐受电压 Uimp ( kV ) | 8 | 12 | 12 | 12 | |
额定工作电流 In ( A ) ③ | A / B | A / B | A / B | A / B | |
AC 400V AC 21A / AC 21B | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |
AC 22A / AC 22B | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |
AC 23A / AC 23B | 250 / 250 | 400 / 400 | 400 / 500 | 800 / 800 | |
AC 690V ④ AC 20 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |
AC 21A / AC 21B | 200 / 250 | 400 / 400 | 500 / 500 | 800 / 800 | |
AC 22 A / AC 22B | 125 / 160 | 250 / 315 | 315 / 315 | 500 / 630 | |
AC 23 A / AC 23B | 100 / 125 | 160 / 200 | 160 / 200 | 200 / 250 | |
DC 400V DC 20 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |
DC 21 A / DC 21B | 250 / 250 | 400 / 400 | 500 / 500 | 630 / 800 | |
DC 22 A / DC 22B | 200 / 200 | 400 / 400 | 500 / 500 | 800 ① / 630 | |
DC 23 A / DC 23B | 200 ① / 200 ① | 400 ① / 315 | 500 ① / 500 ① | 800 ① / 500 | |
耐受冲击电流 ( kA ,峰值) | 30 | 45 | 45 | 55 | |
允许的短时间电流 1s ( kA ) | 9 | 13 | 13 | 26 | |
接通与断开特性 | |||||
分断容量 ( A ) | 2000 | 3200 | 3200 | 6400 | |
AC 400V cosφ = 0 . 35 |
|
|
|
| |
接通容量 AC 400V 、 cosφ = 0 . 35 ( A ) | 2500 | 4000 | 4000 | 8000 | |
短路接通容量 ( kA ,峰值) | 17 | 30 | 30 | 50 | |
寿命② | |||||
机械 ( 操作循环次数,次) | 8000 | 5000 | 5000 | 4000 | |
电气 ( 操作循环次数,次) | 1000 | 1000 | 1000 | 500 | |
连接 | |||||
最小铜缆截面 ( mm2 ) | 95 | 185 | 2 × 150 | 2 × 185 | |
最小铜排截面 ( mm2 ) |
|
| 2 × 30 × 5 | 2 × 40 × 5 | |
最大铜缆截面 ( mm2 ) | 150 | 240 | 2 × 300 | 2 × 300 | |
最大铜排截面 ( mm2 ) | 32 | 40 | 50 | 63 | |
切换时间 | |||||
Ⅰ — 0 —Ⅱ或Ⅱ— 0 —Ⅰ( s ) | 1 . 1 | 1 . 2 | 1 . 2 | 2 . 6 | |
Ⅰ — 0 或 Ⅱ— 0 ( s ) | 0 . 7 | 0 . 8 | 0 . 8 | 1 . 6 | |
电气控制能耗 | |||||
电源电压 : |
|
|
|
| |
DC24 、 48 、 110V 启动 ( W ) | 350 | 420 | 410 | 320 | |
正常 ( W ) | 75 | 90 | 90 | 70 | |
AC 230V 启动 ( VA ) | 350 | 420 | 420 | 320 | |
正常 ( VA ) | 75 | 90 | 90 | 70 | |
质量 ( kg ) | |||||
3 极 | 9 . 5 | 17 | 18 | 26 | |
4 极 | 10 . 5 | 19 | 20 . 5 | 29 | |
约定发热电流 ( 40 ℃, A ) | 1250 | 1600 | 2500 | 3150 | |
额定绝缘电压 Ui ( V ) | 1000 | 1000 | 1000 | 1000 | |
绝缘强度 50Hz1min ( V ) | 10000 | 10000 | 10000 | 10000 | |
额定冲击耐受电压 Uimp ( kV ) | 12 | 12 | 12 | 12 | |
额定工作电流 In ( A ) ③ | A / B | A / B | A / B | A / B | |
AC 400V AC 21A / AC 21B | 1250 / 1250 | 600 / 1600 | 2500 / 2500 | 3150 / 3150 | |
AC 22A / AC 22B | 1250 / 1250 | 1250 / 1250 | 2000 / 2500 | 2500 / 2500 | |
AC 23A / AC 23B | 1000 / 1000 | 1000 / 1000 | 1250 / 1250 | 1250 / 1250 | |
AC 690V ④ AC 20 | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |
AC 21A / AC 21B | 1000 / 1250 | 1600 / 1600 | 2000 / 2500 | 2500 / 2500 | |
AC 22 A / AC 22B | 630 / 800 | 800 / 800 | 1000 / 1000 | 1000 / 1000 | |
AC 23 A / AC 23B | 400 / 500 | 500 / 500 | 800 / 800 | 800 / 800 | |
DC 400V DC20 | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |
DC 21 A / DC 21B | 1250 / 1250 | 1600 / 1600 | 2000 / 2000 | 2000 / 2000 | |
DC 22 A / DC 22B | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | |
DC 23 A / DC 23B | 1000 ① / 1000 ① | 1000 ① / 1000 ① | 1000 ① / 1000 ① | 1000 ① / 1000 ① | |
耐受冲击电流 ( kA ,峰值) | 105 | 110 | 110 | 120 | |
允许的短时间电流 1s ( kA ) | 50 | 50 | 50 | 55 | |
接通与断开特性 | |||||
分断容量 AC 400V cosφ = 0 . 35 ( A ) | 8000 | 8000 | 10000 | 10000 | |
接通容量 AC 400V cosφ = 0 . 35 ( A ) | 8000 | 10000 | 12500 | 12500 | |
短路接通容量 ( kA ,峰值) | 70 | 70 | 80 | 85 | |
寿命② | |||||
机械 ( 操作循环次数,次) | 4000 | 3000 | 2500 | 2500 | |
电气 ( 操作循环次数,次) | 500 | 500 | 500 | 500 | |
连接 | |||||
最小铜缆截面 ( mm2 ) |
|
|
|
| |
最小铜排截面 ( mm2 ) | 2 × 60 × 5 | 2 × 80 × 5 | 4 × 100 × 5 | 2 × 100 × 5 | |
最大铜缆截面 ( mm2 ) | 41 × 85 | 6 × 240 |
|
| |
最大铜排截面 ( mm2 ) | 100 | 125 | 125 | 125 | |
切换时间 | |||||
Ⅰ — 0 —Ⅱ或Ⅱ— 0 —Ⅰ( s ) | 2 . 6 | 2 . 6 | 3 . 6 | 3 . 6 | |
Ⅰ — 0 或 Ⅱ— 0 ( s ) | 1 . 6 | 1 . 6 | 2 . 1 | 2 . 1 | |
电气控制能耗 | |||||
电源电压 : |
|
|
|
| |
DC24 、 48 、 110V | 启动 ( W ) | 340 | 350 | 780 | 800 |
正常 ( W ) | 80 | 95 | 210 | 220 | |
AC 230V | 启动 VA ) | 340 | 350 | 780 | 800 |
正常 ( VA ) | 80 | 95 | 210 | 220 | |
质量 ( kg ) | |||||
3 极 | 30 | 40 | 80 | 114 | |
4 极 | 36 | 48 . 5 | 98 | 135 | |
注 :①按极性两电极串联使用。 ②更长的寿命请向该公司查询。 ③“ A ”类型为频繁操作 ,“ B ”类型为不频繁操作。 ④带端子护罩或相分隔屏。 | |||||