SIRCOVER 系列转换开关电气和机械特性 | |||||||||
约定发热电流 ( 40 ℃, A ) | 125 | 160 | 250 | 400 | 630 | 800 | |||
额定绝缘电压 Ui ( V ) | 750 | 750 | 750 | 1000 | 1000 | 1000 | |||
50Hz1min 绝缘强度 ( V ) | 5000 | 5000 | 5000 | 8000 | 8000 | 8000 | |||
额定冲击耐受电压 Uimp ( kA ) | 8 | 8 | 8 | 12 | 12 | 12 | |||
额定工作电流 In ( A ) ② | A / B | A / B | A / B | A / B | A / B | A / B | |||
AC400V AC 21 A / AC 21 B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
AC 22 A / AC 22B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
AC 23 A / AC 23B | 125 / 125 | 125 / 160 | 250 / 250 | 400 / 400 | 400 / 500 | 800 / 800 | |||
AC500V AC 21 A / AC 21 B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
AC 22 A / AC 22B | 125 / 125 | 125 / 125 | 250 / 250 | 400 / 400 | 500 / 500 | 800 / 800 | |||
AC 23 A / AC 23B | 100 / 100 | 100 / 100 | 200 / 250 | 315 / 315 | 315 / 315 | 630 / 800 | |||
AC690V ④ AC 20 A / AC 20 B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
AC 21 A / AC 21 B | 125 / 125 | 160 / 160 | 200 / 250 | 400 / 400 | 500 / 500 | 800 / 800 | |||
AC 22 A / AC 22B | 125 / 125 | 125 / 125 | 125 / 160 | 250 / 315 | 315 / 315 | 500 / 630 | |||
AC 23 A / AC 23B | 63 / 80 | 63 / 80 | 100 / 125 | 160 / 200 | 160 / 200 | 200 / 250 | |||
DC260V DC 20 A / DC 20B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
DC 21 A / DC 21B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
DC 22 A / DC 22B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 500 / 500 | 800 / 800 | |||
DC 23 A / DC 23B | 125 / 125 | 125 / 125 | 200 / 200 | 400 / 400 | 500 / 500 | 800 / 800 | |||
DC400V DC 20 A / DC 20B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
DC 21 A / DC 21B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 500 / 500 | 630 / 800 | |||
DC 22 A / DC 22B | 125 / 125 | 125 / 125 | 200 / 200 | 400 / 400 | 500 / 500 | 800 ① / 630 | |||
DC 23 A / DC 23B | 125 ① / 100 | 125 ① / 125 ① | 200 ① / 200 ① | 400 ① / 315 | 500 ① / 500 ① | 800 ① / 500 | |||
DC500V DC 20 A / DC 20B | 125 / 125 | 160 / 160 | 250 / 250 | 400 / 400 | 630 / 630 | 800 / 800 | |||
DC 21 A / DC 21B | 125 / 125 | 125 / 125 | 200 / 200 | 400 / 400 | 500 / 500 | 630 / 630 | |||
DC 22 A / DC 22B | 125 / 125 | 125 / 125 | 200 / 200 | 315 / 400 | 500 / 500 | 800 ① / 500 | |||
DC 23 A / DC 23B | 125 ① / 80 | 125 ① / 125 ① | 200 ① / 200 ① | 400 ① / 250 | 500 ① / 500 ① | 800 ① / 500 | |||
电动机功率 ( kW )③ | |||||||||
AC 400V 无预断开辅触点 | 63 / 63 | 63 / 80 | 132 / 132 | 220 / 220 | 220 / 280 | 450 / 450 | |||
AC 500V 无预断开辅触点 | 63 / 63 | 63 / 63 | 140 / 160 | 220 / 220 | 220 / 220 | 450 / 560 | |||
AC 690V 无预断开辅触点 | 55 / 75 | 55 / 75 | 90 / 110 | 150 / 185 | 150 / 185 | 185 / 220 | |||
AC 400V 有预断开辅触点 | 63 / 63 | 80 / 80 | 132 / 132 | 220 / 220 | 355 / 355 | 450 / 450 | |||
AC 500V 有预断开辅触点 | 80 / 80 | 80 / 80 | 160 / 160 | 280 / 280 | 355 / 355 | 560 / 560 | |||
AC 690V 有预断开辅触点 | 110 / 110 | 110 / 110 | 110 / 110 | 220 / 295 | 295 / 295 | 475 / 600 | |||
无功功率 AC 400V ( kvar ) | 55 | 60 | 100 | 150 | 2 × 125 | 2 × 150 | |||
耐冲击电流 ( kA ,峰值) | 20 | 20 | 30 | 45 | 45 | 55 | |||
允许的短时间电流 1s ( kA ) | 7 | 7 | 9 | 13 | 13 | 26 | |||
接通与断开特性 | |||||||||
分断容量 AC 400V cosφ = 0 . 35 ( A ) | 1000 | 1000 | 2000 | 3200 | 3200 | 6400 | |||
接通容量 AC 400V cosφ = 0 . 35 ( A ) | 1250 | 1250 | 2500 | 4000 | 4000 | 8000 | |||
短路接通容量 ( kA ,峰值) | 12 | 12 | 17 | 30 | 30 | 50 | |||
寿命 | |||||||||
机械 ( 操作循环次数,次) | 10000 | 8000 | 8000 | 5000 | 5000 | 4000 | |||
电气 ( 操作循环次数,次) | 1000 | 1000 | 1000 | 1000 | 1000 | 500 | |||
操作力 ( N · m ) | 9 . 5 | 9 . 5 | 11 | 17 | 17 | 37 | |||
连接 | |||||||||
最小铜缆截面 ( mm2 ) | 35 | 50 | 95 | 185 | 2 × 150 | 2 × 185 | |||
最大铜排截面 ( mm2 ) |
|
|
|
| 2 × 30 × 5 | 2 × 40 × 5 | |||
最大铜缆截面 ( mm2 ) | 50 | 95 | 150 | 240 | 2 × 300 | 2 × 300 | |||
最小铜排截面 ( mm2 ) | 25 | 25 | 32 | 40 | 50 | 63 | |||
质量 ( kg ) | |||||||||
3 极直接操作 | 2 . 5 | 3 | 4 | 9 . 5 | 11 | 17 . 5 | |||
4 极直接操作 | 3 | 3 | 5 | 11 | 13 | 21 | |||
约定发热电流 ( 40 ℃, A ) | 1250 | 1600 | 2500 | 3150 | |||||
额定绝缘电压 Ui ( V ) | 1000 | 1000 | 1000 | 1000 | |||||
绝缘强度 50Hz1min ( V ) | 10000 | 10000 | 10000 | 10000 | |||||
额定冲击耐受电压 Uimp ( kA ) | 12 | 12 | 12 | 12 | |||||
额定工作电流 In ( A ) ② | A / B | A / B | A / B | A / B | |||||
AC400V AC 21 A / AC 21 B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
AC 22 A / AC 22B | 1250 / 1250 | 1250 / 1250 | 2000 / 2500 | 2500 / 2500 | |||||
AC 23 A / AC 23B | 1000 / 1000 | 1000 / 1000 | 1250 / 1250 | 1250 / 1250 | |||||
AC500V AC 21 A / AC 21 B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
AC 22 A / AC 22B | 1000 / 1250 | 1250 / 1250 | 1600 / 2000 | 2000 / 2000 | |||||
AC 23 A / AC 23B | 800 / 1000 | 1000 / 1000 | 1000 / 1000 | 1000 / 1000 | |||||
AC690V ④ AC 20 A / AC 20 B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
AC 21 A / AC 21 B | 1000 / 1250 | 1600 / 1600 | 2000 / 2500 | 2000 / 2500 | |||||
AC 22 A / AC 22B | 630 / 800 | 800 / 800 | 1000 / 1000 | 1000 / 1000 | |||||
AC 23 A / AC 23B | 400 / 500 | 500 / 500 | 800 / 800 | 800 / 800 | |||||
DC260V DC 20 A / DC 20B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
DC 21 A / DC 21B | 1250 / 1250 | 1600 / 1600 | 2000 / 2500 | 2000 / 2500 | |||||
DC 22 A / DC 22B | 1250 / 1250 | 1250 / 1250 | 1250 / 1600 | 1250 / 1600 | |||||
DC 23 A / DC 23B | 1250 ① / 1250 ① | 1250 ① / 1250 ① | 1250 ① / 1250 ① | 1250 ① / 1250 ① | |||||
DC400V DC 20 A / DC 20B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
DC 21 A / DC 21B | 1250 / 1250 | 1600 / 1600 | 2000 / 2000 | 2000 / 2000 | |||||
DC 22 A / DC 22B | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | |||||
DC 23 A / DC 23B | 1000 ① / 1000 ① | 1000 ① / 1000 ① | 1000 ①/ 10050 ① | 1000 ① / 1000 ① | |||||
DC500V DC 20 A / DC 20B | 1250 / 1250 | 1600 / 1600 | 2500 / 2500 | 3150 / 3150 | |||||
DC 21 A / DC 21B | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | 1250 / 1250 | |||||
DC 22 A / DC 22B | 1250 ① / 1250 ① | 1250 ① / 1250 ① | 1250 ① / 1250 ① | 1250 / 1250 | |||||
DC 23 A / DC 23B | 1000 ① / 1000 ① | 1000 ① / 1000 ① | 1000 ①/ 10050 ① | 1000 ① / 1000 ① | |||||
电动机功率 ( kW )③ | |||||||||
AC 400V 无预断开辅触点 | 560 / 560 | 560 / 560 | 710 / 710 | 710 / 710 | |||||
AC 500V 无预断开辅触点 | 560 / 710 | 710 / 710 | 710 / 710 | 710 / 710 | |||||
AC 690V 无预断开辅触点 | 400 / 475 | 475 / 475 | 750 / 750 | 750 / 750 | |||||
AC 500V 有预断开辅触点 | 710 / 710 | 710 / 710 | 1100 / 1100 | 1100 / 1100 | |||||
AC 500V 有预断开辅触点 | 710 / 900 | 900 / 900 | 1100 / 1100 | 1100 / 1100 | |||||
AC 500V 有预断开辅触点 | 600 / 750 | 750 / 750 | 900 / 900 | 900 / 900 | |||||
无功功率 AC 400V ( kvar ) | 4 × 125 | 5 × 150 | 7 × 150 | 9 × 150 | |||||
耐冲击电流 ( kA ,峰值) | 105 | 110 | 110 | 120 | |||||
允许的短时间电流 1s ( kA ) | 50 | 50 | 50 | 50 | |||||
接通与断开特性 | |||||||||
分断容量 AC 400V cosφ = 0 . 35 ( A ) | 8000 | 8000 | 10000 | 10000 | |||||
接通容量 AC 400V cosφ = 0 . 35 ( A ) | 10000 | 10000 | 12500 | 12500 | |||||
短路接通容量 ( kA ,峰值) | 70 | 70 | 80 | 85 | |||||
寿命 | |||||||||
机械 ( 操作循环次数,次) | 4000 | 3000 | 2500 | 2500 | |||||
电气 ( 操作循环次数,次) | 500 | 500 | 500 | 500 | |||||
操作力 ( N · m ) | 37 | 42 | 60 | 60 | |||||
连接 | |||||||||
最小铜缆截面 ( mm2 ) |
|
|
|
| |||||
最小铜排截面 ( mm2 ) | 2 × 60 × 5 | 2 × 80 × 5 | 4 × 100 × 5 | 4 × 100 × 5 | |||||
最大铜缆截面 ( mm2 ) | 4 × 185 | 6 × 240 | — | — | |||||
最大铜排截面 ( mm2 ) | 100 | 125 | 125 | 125 | |||||
质量 ( kg ) | |||||||||
3 极直接操作 | 22 . 5 | 34 | 72 | 98 | |||||
4 极直接操作 | 27 . 5 | 42 | 88 | 110 | |||||