10kV输电线路末端短路容量计算
10kV输电线路末端短路容量计算 | |||||||||||||
Sdx (MVA) | 线路 种类 | 输电线路长度L(km) | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 15 | 20 | ||
末端短路容量Sdl(MVA) | |||||||||||||
30 | 架空 | 27.5 | 25.4 | 23.6 | 22.0 | 20.6 | 19.4 | 18.4 | 17.4 | 16.5 | 15.7 | 12.7 | 10.7 |
电缆 | 29.4 | 28.8 | 28.3 | 27.7 | 27.2 | 26.7 | 26.3 | 25.8 | 25.3 | 24.9 | 23.0 | 21.3 | |
50 | 架空 | 43.4 | 38.4 | 34.4 | 31.2 | 28.5 | 26.2 | 24.3 | 22.6 | 21.2 | 19.9 | 15.3 | 12.4 |
电缆 | 48.4 | 46.8 | 45.4 | 44.0 | 42.7 | 41.5 | 40.4 | 39.3 | 38.3 | 37.3 | 33.1 | 29.8 | |
75 | 架空 | 61.1 | 51.6 | 44.7 | 39.3 | 35.2 | 31.8 | 29.0 | 26.7 | 24.7 | 23.0 | 17.1 | 13.6 |
电缆 | 71.4 | 68.1 | 65.0 | 62.3 | 59.8 | 57.4 | 55.3 | 53.3 | 51.4 | 49.7 | 42.5 | 37.1 | |
100 | 架空 | 76.8 | 62.3 | 52.5 | 45.3 | 39.8 | 35.6 | 32.1 | 29.3 | 26.9 | 24.9 | 18.1 | 14.2 |
电缆 | 93.6 | 88.0 | 83.1 | 78.6 | 74.6 | 71.0 | 67.8 | 64.8 | 62.0 | 59.5 | 49.5 | 42.4 | |
200 | 架空 | 124.7 | 90.6 | 71.1 | 58.5 | 49.8 | 43.3 | 38.3 | 34.3 | 31.1 | 28.4 | 19.9 | 15.3 |
电缆 | 176.1 | 157.2 | 142.0 | 129.5 | 119.0 | 110.1 | 102.5 | 95.8 | 89.9 | 84.7 | 65.8 | 53.8 | |
300 | 架空 | 157.4 | 106.7 | 80.7 | 64.9 | 54.2 | 46.6 | 40.9 | 36.4 | 32.8 | 29.8 | 20.6 | 15.7 |
电缆 | 249.2 | 213.1 | 186.1 | 165.2 | 148.5 | 134.9 | 123.6 | 114.0 | 105.8 | 98.7 | 73.9 | 59.1 | |
350 | 架空 | 170.2 | 112.4 | 83.9 | 66.9 | 55.7 | 47.7 | 41.7 | 37.0 | 33.3 | 30.3 | 20.8 | 15.8 |
电缆 | 282.7 | 237.1 | 204.2 | 179.3 | 159.8 | 144.2 | 131.3 | 120.5 | 111.4 | 103.6 | 76.6 | 60.8 | |
500 | 架空 | 199.2 | 124.4 | 90.4 | 71.0 | 58.5 | 49.7 | 43.2 | 38.2 | 34.3 | 31.1 | 21.1 | 16.0 |
电缆 | 373.1 | 297.6 | 247.5 | 211.9 | 185.2 | 164.5 | 147.9 | 134.4 | 123.2 | 113.6 | 82.0 | 64.1 | |
∞ | 架空 | 331.1 | 165.6 | 110.4 | 82.8 | 66.2 | 55.2 | 47.3 | 41.4 | 36.8 | 33.1 | 22.1 | 16.6 |
电缆 | 1470.6 | 735.3 | 490.2 | 367.6 | 294.1 | 245.1 | 210.1 | 183.8 | 163.4 | 147.1 | 98.0 | 73.5 | |