6/1kV电力电缆结构尺寸及电气特性
0.6/1kV电力电缆结构尺寸及电气特性 | |||||||||||
标称截面 | 绝缘厚度 | 外护套厚度(mm) | 电缆近似外径(mm) | ||||||||
(mm2) | (mm) | 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c |
1.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 5.9 | 10.4 | 10.8 | 11.6 | 12.4 |
2.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6.3 | 11.2 | 11.7 | 12.6 | 13.5 |
4 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6.8 | 12.2 | 12.7 | 13.7 | 14.8 |
6 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 7.3 | 13.2 | 13.8 | 14.9 | 16.1 |
10 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 8.6 | 15.8 | 16.6 | 18.0 | 19.6 |
16 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 9.7 | 17.9 | 18.9 | 20.6 | 22.4 |
25 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 11.4 | 21.3 | 22.6 | 24.8 | 27.2 |
35 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.9 | 12.5 | 23.6 | 25.1 | 27.6 | 30.5 |
50 | 1.0 | 1.4 | 1.8 | 1.9 | 2.0 | 2.1 | 14.1 | 26.7 | 28.5 | 31.6 | 35.0 |
70 | 1.1 | 1.5 | 1.9 | 2.0 | 2.1 | 2.3 | 16.2 | 31.0 | 33.2 | 36.8 | 40.8 |
95 | 1.1 | 1.5 | 2.1 | 2.2 | 2.3 | 2.4 | 18.3 | 35.1 | 37.6 | 41.8 | 46.4 |
120 | 1.2 | 1.6 | 2.2 | 2.3 | 2.4 | 2.6 | 20.2 | 39.0 | 41.8 | 46.5 | 51.7 |
150 | 1.4 | 1.7 | 2.3 | 2.4 | 2.6 | 2.8 | 22.3 | 43.3 | 46.4 | 51.6 | 57.4 |
185 | 1.6 | 1.7 | 2.5 | 2.6 | 2.8 | 3.0 | 24.8 | 48.2 | 51.7 | 57.6 | 64.1 |
240 | 1.7 | 1.8 | 2.7 | 2.8 | 3.0 | 3.3 | 27.9 | 54.3 | 58.3 | 64.9 | 72.3 |
300 | 1.8 | 1.9 | 2.9 | 3.0 | 3.3 | 3.5 | 30.7 | 60.0 | 64.4 | 71.8 | 80.0 |
400 | 2.0 | 2.0 | — | — | — | — | 34.3 | — | — | — | — |
500 | 2.2 | 2.2 | — | — | — | — | 38.6 | — | — | — | — |