预分支电力电缆的技术指标
预分支电力电缆的技术指标 | |||||||||||
导 线 | 绝缘厚度 (mm) | 外套厚度 (mm) | 外径(约) (mm) | 重量(约) (kg/km) | 交流试验电压 (kV/5min) | 最大导线电阻 (Ω/km) | 额定电流 (A) | 电压降 (V/A·m×10-3) | |||
标称截面(mm2) | 形状和结构 | 直径(mm) | |||||||||
10 | 圆形紧 压绞线 | 3.7 | 1.0 | 1.4 | 9.0 | 150 | 3.5 | 1.83 | 71 | 2.0 | |
16 | 4.7 | 1.0 | 1.4 | 10.0 | 215 | 3.5 | 1.15 | 94 | 1.3 | ||
25 | 5.9 | 1.2 | 1.4 | 11.3 | 310 | 3.5 | 0.727 | 122 | 0.84 | ||
35 | 7.0 | 1.2 | 1.4 | 12.3 | 410 | 3.5 | 0.524 | 151 | 0.63 | ||
50 | 8.5 | 1.4 | 1.4 | 14.0 | 570 | 3.5 | 0.387 | 183 | 0.49 | ||
70 | 10.1 | 1.4 | 1.4 | 15.7 | 770 | 3.5 | 0.268 | 231 | 0.36 | ||
95 | 11.7 | 1.6 | 1.7 | 18.4 | 1030 | 3.5 | 0.193 | 284 | 0.29 | ||
120 | 13.2 | 1.6 | 1.7 | 19.8 | 1280 | 3.5 | 0.153 | 327 | 0.24 | ||
150 | 14.7 | 1.8 | 1.8 | 22.8 | 1590 | 3.5 | 0.124 | 368 | 0.21 | ||
185 | 16.4 | 2.0 | 1.8 | 25.1 | 1950 | 3.5 | 0.0991 | 437 | 0.19 | ||
240 | 18.6 | 2.2 | 1.8 | 28.5 | 2490 | 3.5 | 0.0754 | 522 | 0.16 | ||
300 | 20.8 | 2.4 | 2.1 | 32.0 | 3140 | 3.5 | 0.0601 | 606 | 0.15 | ||
400 | 24.1 | 2.6 | 2.2 | 35.4 | 4140 | 3.5 | 0.0470 | 732 | 0.131 | ||
500 | 26.9 | 2.8 | 2.3 | 40.0 | 5140 | 3.5 | 0.0366 | 854 | 0.120 | ||
630 | 30.2 | 2.8 | 2.4 | 46.0 | 6440 | 3.5 | 0.0283 | 1024 | 0.111 | ||
800 | 34.8 | 2.8 | 2.6 | 50.0 | 8450 | 3.5 | 0.0221 | 1206 | 0.104 | ||
1000 | 39.0 | 2.8 | 2.6 | 52.0 | 10600 | 3.5 | 0.0176 | 1379 | 0.098 | ||
说明:额定电流和电压降根据下列条件计算: 1.导线温度70℃ 2.导线温度40℃ 3.电缆排列(单芯)S=2d 4.功率因数cosφ=0.8 5.Vd代表电压降:Vd=K×I×L×Vo(V) |
| 式中 I——电流,(A); L——线路长度,(m); Vo——电压降,(V/A·m×10-3) K——系数,根据配电系统确定三相四线制; 相——中线间K=1; 相——相线间K= | |||||||||

。