ABB断路器选择性配合
ABB断路器选择性配合(电源侧断路器In<160A) | ||||||||||||||
选择性配合表 | 负载侧断路器 In(A) | S500D | S290D | S1 S2 S3 | S1 S2 | S1 S2 S3 | S1 S2 S3 | S1 S2 S3 | S4 (b) | |||||
电源侧断路器 In(A) |
| 32 | 40 | 50 | 63 | 80 | 100 | 125 | ≤50 | 63 | 80 | 100 | 125 | ≤160 |
S240 S250 S260 S270 S280 S290 | Z-B-C-K-D≤2A | T | T | T | T | T | T | T | T | T | T | T | T | T |
Z-B-C-K-D 3A | 3 | 6 | T | T | T | T | T | T | T | T | T | T | T | |
Z-B-C-K-D 4A | 2 | 3 | 6 | T | T | T | T | T | T | T | T | T | T | |
Z-B-C-K-D 6A | 1.5 | 2 | 3 | 5 | 10 | T | T | 5 | 10 | T | T | T | T | |
Z-B-C-K-D 8A | 1.5 | 2 | 3 | 5.5 | 10.5 | T | T | 5.5 | 10.5 | T | T | T | T | |
Z-B-C-K-D 10A | 1 | 1.5 | 2 | 3 | 5 | 8 | 16 | 3 | 5 | 8.5 | 17 | T | T | |
K-D 13~16A | — | 1 | 1.5 | 2 | 3 | 5 | 7.5 | 2 | 3 | 5 | 8 | 13.5 | T | |
Z-B-C 13~16A | 1 | 1.5 | 2 | 3 | 4.5 | 7 | 11.5 | 3 | 4.5 | 7.5 | 12 | 20 | T | |
K-D 20A | — | — | — | 2 | 3 | 7 | 6.5 | 2 | 3 | 4.5 | 6.5 | 11 | T | |
Z-B-C 20~25A | — | 1.5 | 2 | 2.5 | 3.5 | 5 | 8 | 2.5 | 3.5 | 5.5 | 8 | 13.5 | T | |
K-D 25~32A | — | — | — | — | 2.5 | 4 | 6 | — | 2.5 | 4 | 6 | 9.5 | T | |
Z-B-C 32~40A | — | — | — | 2 | 3 | 4.5 | 7 | 2 | 3 | 4.5 | 7 | 12 | T | |
K-D 40A | — | — | — | — | — | — | 5 | — | — | — | 5 | 8 | T | |
Z-B-C 50~63A | — | — | — | — | — | 3 | 4.5 | — | — | 3 | 4.5 | 6 | T | |
K-D 50~63A | — | — | — | — | — | — | — | — | — | — | — | — | T | |
S500 B-C-D | ≤16A | — | — | — | — | 6 | 10 | T | 4.5 | 6 | 10 | 15 | 35 | 40 |
20A | — | — | — | — | 6 | 7.5 | 10 | 4.5 | 6 | 7.5 | 15 | 35 | 40 | |
25A | — | — | — | — | 4.5 | 6 | 10 | — | 4.5 | 7.5 | 10 | 20 | 40 | |
32A | — | — | — | — | — | 6 | 10 | — | — | 6 | 10 | 20 | 40 | |
40A | — | — | — | — | — | — | 7.5 | — | — | — | 7.5 | 15 | 40 | |
50A | — | — | — | — | — | — | — | — | — | — | — | 10 | 40 | |
S500K | ≤5.8A | — | — | — | — | T | T | T | 35 | 35 | 35 | 35 | 35 | 40 |
8A | — | — | — | — | 10 | T | T | 4.5 | 10 | 35 | 35 | 35 | 40 | |
11A | — | — | — | — | 7.5 | T | T | 3 | 7.5 | 25 | 35 | 35 | 40 | |
15A | — | — | — | — | 4.5 | 10 | T | 3 | 4.5 | 10 | 15 | 30 | T | |
20A | — | — | — | — | 4.5 | 6 | 10 | — | 3 | 6 | 10 | 20 | T | |
26A | — | — | — | — | — | 4.5 | 7.5 | — | — | — | 7.5 | 15 | T | |
32A | — | — | — | — | — | — | 7.5 | — | — | — | 7.5 | 15 | T | |
37A | — | — | — | — | — | — | — | — | — | — | — | 10 | T | |