断路器当以环境温度40℃为基准整定的温度修正值
断路器当以环境温度40℃为基准整定的温度修正值 | |||||||||
整定电流 (A) | 在下列环境温度时,整定电流修正值 | ||||||||
20℃ | 25℃ | 30℃ | 35℃ | 40℃ | 45℃ | 50℃ | 55℃ | 60℃ | |
50 | 57.5 | 56.0 | 54.0 | 52.0 | 50.0 | 48.0 | 45.5 | 43.5 | 41.0 |
63 | 72.5 | 70.5 | 68.0 | 65.5 | 63.0 | 60.5 | 57.5 | 54.5 | 51.5 |
80 | 92.0 | 89.0 | 86.0 | 83.0 | 80.0 | 76.5 | 73.5 | 69.5 | 66.0 |
100 | 115.0 | 111.5 | 108.0 | 104.0 | 100.0 | 96.0 | 91.5 | 87.0 | 82.5 |