熔断器与断路器选择性配合
熔断器与断路器选择性配合 | ||||||||||
上级 | 上级熔断器熔体额定电流(A) | |||||||||
分断电流(kA) | ||||||||||
下级 | 20 | 25 | 32 | 50 | 63 | 80 | 100 | 125 | 160 | |
断路器过电流 脱扣器整定电流 (A) | 6 | 0.5 | 0.8 | 2.0 | 3.3 | 5.5 | 6.0 | 6.0 | 6.0 | 6.0 |
10 | 0.4 | 0.7 | 1.5 | 0 | 3.5 | 5.0 | 6.0 | 6.0 | 6.0 | |
16 |
|
| 1.3 | 2.0 | 2.9 | 4.1 | 6.0 | 6.0 | 6.0 | |
20 |
|
|
| 1.8 | 2.6 | 3.5 | 5.0 | 6.0 | 6.0 | |
25 |
|
|
| 1.8 | 2.6 | 3.5 | 5.0 | 6.0 | 6.0 | |
32 |
|
|
|
| 2.2 | 3.0 | 4.0 | 6.0 | 6.0 | |
40 |
|
|
|
|
| 2.5 | 4.0 | 6.0 | 6.0 | |
50 |
|
|
|
|
|
| 3.5 | 5.0 | 6.0 | |
63 |
|
|
|
|
|
| 3.5 | 5.0 | 6.0 | |