10kV级SCR-10系列H级绝缘(赛格迈)干式变压器
10kV级SCR系列H级绝缘(赛格迈)干式电力变压器技术数据 | |||||||||
型号 | 额定容量 (kVA) | 额定电压(kV) | 连接组 标号 | 空载损耗 (W) | 负载损耗 (W) | 空载电流 (%) | 短路阻抗 (%) | 噪声 (dB) | |
高压 | 低压 | ||||||||
SCR-30/10 | 30 | 6±5% 或 ±2×2.5% 6.3±5% 或 ±2×2.5% 10±5% 或 ±2×2.5% | 0.4 | Y,yn0 或 D,yn11 | 240 | 890 | 3 | 4 | 50 |
SCR-50/10 | 50 | 340 | 1260 | 2.8 | 4 | 50 | |||
SCR-63/10 | 63 | 440 | 1600 | 2.8 | 4 | — | |||
SCR-80/10 | 80 | 460 | 1740 | 2.8 | 4 | 52 | |||
SCR-100/10 | 100 | 500 | 1900 | 2.8 | 4 | 52 | |||
|
|
|
|
|
|
| |||
SCR-125/10 | 125 | 590 | 2330 | 2 | 4 | 52 | |||
SCR-160/10 | 160 | 680 | 2680 | 2 | 4 | 52 | |||
SCR-200/10 | 200 | 780 | 3100 | 2 | 4 | 54 | |||
SCR-250/10 | 250 | 900 | 3300 | 1.8 | 4 | 54 | |||
SCR-315/10 | 315 | 1100 | 4000 | 1.8 | 4 | 56 | |||
|
|
|
|
|
|
| |||
SCR-400/10 | 400 | 1220 | 4500 | 1.8 | 4 | 56 | |||
SCR-500/10 | 500 | 1450 | 5500 | 1.8 | 4 | 58 | |||
SCR-630/10 | 630 | 1600 | 6500 | 1.8 | 6 | 58 | |||
SCR-800/10 | 800 | 1800 | 7800 | 1.3 | 6 | 60 | |||
SCR-1000/10 | 1000 | 2150 | 9100 | 1.3 | 6 | 60 | |||
|
|
|
|
|
|
| |||
SCR-1250/10 | 1250 | 2550 | 11000 | 1.3 | 6 | 62 | |||
SCR-1600/10 | 1600 | 3000 | 12000 | 1.3 | 6 | 62 | |||
SCR-2000/10 | 2000 | 3500 | 15000 | 1.2 | 6 | 64 | |||
SCR-2500/10 | 2500 | 4000 | 18000 | 1.2 | 6 | 64 | |||